1.1 Hour Run Meter
Display: 9999.99
Operating Voltage: AC 100V / 200–250V / 380V
Accuracy Class: 0.5
1.2 Phase Sequence Indicator
Operating Voltage: AC 100–150V / 150–500V
Operating Frequency: 50Hz, 60Hz
1.3 Digital Synchorscope (with Relay Output)
Relay Output A
1. Voltage difference between UB and UGEN is less than pre-set value, S1 (△U × UN);
2. Frequency difference between FGEN and FBUS is less than pre-set value, S2 (△F);
3. Pre-set time difference before phase difference is 0°, S3 (Time);
When the above 3 conditions are satisfied, synchronized signal will be released.
Relay Output B
Voltage difference between UBB and UGEN is less than pre-set value S1 (△U × UN); phase difference between UBB and UGEN satisfies pre-set value S2 (△φ), and within the pre-set delay time (Delay), phase difference between UBB and UGEN is still satisfied with pre-set value S2 (△φ) — synchronized signal will be released.
Operating Voltage: AC 57V / 100V / 220V / 380V / 415V / 440V
Operating Frequency: 50Hz, 60Hz
Accuracy Class: 15° (Electrical angle 15°~345°) | 3° (Electrical angle 345°~15°)
1.4 Double Meter
Measuring Range: 0–10V to 500V
Accuracy Class: 1.5
Measuring Range: 0–5A (Connection on CT)
Accuracy Class: 1.5
1.5 Net Insulation Monitor (MΩ Meter)
a Integrated Net Insulation Monitor — Monitor with measuring system. Can be customized with self-detection.
Operating Modes:
🔵 "Monitor" mode: Ordinary monitoring — works as normal.
⚪ "Suspend" mode: Invalid — monitor does not check insulation resistance; pointer points at ∞.
🔴 "Test" mode: Self-detection — monitor does not check insulation resistance; pointer points at 0, alarm LED lit, relay activated.
b Separated Net Insulation Monitor — Monitor and measuring system are separated.
c Integrated Double Circuits Net Insulation Monitor — Monitors the insulation resistance of two ungrounded power networks simultaneously.
1) & 2) Relay (Load Resistance): DC 30V, 5A | AC 250V, 5A
NO Normally Open: When value is less than alarm limit, relay operates — normally open changes from break to closed.
NC Normally Close: When value is greater than alarm limit, relay operates. Until the value is less than alarm limit or meter power is cut off, relay releases — normally close contact breaks connection and closes.
Max. Voltage of Measuring Circuit: AC 500V / 690V
Measuring Range: 0–1MΩ | 0–5MΩ | 0–10MΩ
Auxiliary Power: AC 57.7 / 100 / 220 / 380 / 450V
Accuracy Class: 1.5