Inquiry Now
Leave Your Message

Multifunctional Power Instrument LCD: China Suppliers & Factory for Accurate Electrical Monitoring Solutions

Discover our multifunctional power instrument, expertly designed and manufactured in China to meet the electrical monitoring needs of power distribution systems. This advanced device precisely measures key electrical characteristics, including three-phase voltage, three-phase current, active power, reactive power, frequency, power factor, and four-quadrant energy. With a long-lasting LCD display, users can easily view measurement parameters and system performance data, Our reliable power instrument features an RS485 communication interface, utilizing the MODBUS RTU protocol for seamless connectivity. The intuitive design includes four programmable buttons on the instrument panel, allowing for handy switching and flexible parameter configuration. Trust our factory to provide you with high-quality power monitoring solutions that cater to your unique requirements. Partner with leading suppliers for exceptional performance and durability in electrical measurements

    Product Overview

    There are several different types of extended function modules to choose from: The four-channel analog quantity (0~20mA/4~20mA) output can transmit electrical quantity, while the four-channel switching value input and output can monitor and control local or long-range switch signals ("remote signaling" and "remote control"). The device may immediately replace a typical power transmitter, a measuring indication instrument, an electric energy measuring instrument, and any associated auxiliary units. With modular structural design, customers may select the most cost-effective functional configuration based on their specific requirements.


    It is frequently utilized in applications such as energy management systems, supply and distribution network automation, district power control, and entire switchgear sets. It has the benefit of easy installation and maintenance. Sample wiring, small quantity, programmable input parameters, and networkable with various PLCs, industry control computer communications software.

    • 4-Channel Analog Output
      0~20mA / 4~20mA for transmitting electrical quantities
    • 🔁 Switching Value I/O
      4-channel input & output for remote signaling and control
    • 🔌 Modular Design
      Cost-effective configuration tailored to specific requirements
    • 🏭 Wide Application
      Energy management, distribution automation & switchgear sets
    • 🔗 PLC Compatible
      Networkable with PLCs and industrial control computer software
    Technical Parameters
    📋 The following tables detail the complete technical specifications of this power meter, including input/output, accuracy, safety and environment parameters.
    ⚙️ Input / Output — Electrical Parameters

    Technical parameters

    Index

    Input

    Network

    Three-phase three-wire, three-phase four-wire

    Voltage

    Rated value

    AC 0~500V

    Over load

    Consistent 1.2 times instantaneous, 2 times / 30s

    Consumption

    <0.5VA (each phase)

    Impedance

    >500kΩ

    Current

    Rated value

    AC 1A, 5A

    Over load

    Consistent: 1.2 times instantaneous, 2 times / 1s

    Impedance

    <2mΩ

    Frequency

    45–65Hz

    Output

    Electric energy

    Output mode

    Two-channel open-collector, optical coupling pulse output

    Pulse constant

    Active: 3200 imp/kWh
    Reactive: 3200 imp/kVARh

    Start

    On the condition of rated voltage, reference frequency and cosφ=1.0, when load operational current is 0.01In, it can start and measure the electric energy continuously.

    Creep

    When executing 115% rated voltage and no current in the current circuitry, the instrument has no electric energy accumulation and pulse output.

    📡 Communication, Analog & Switching Output / Input

    Output

    Communication

    Output mode

    RS485

    Protocol

    MODBUS_RTU

    Baud rate

    1200, 2400, 4800, 9600

    Analog quantity

    Channel quantity

    4 channels

    Output mode

    0–20mA, 4–20mA

    Load ability

    <400Ω

    Switching value

    Channel quantity

    4 channels

    Output mode

    Normally open relay contact output

    Contact capability

    AC 240V / 2A

    Switching value input

    Four channel dry contact input modes

    Display mode

    LCD (Blue backlighting)

    Measuring accuracy

    Voltage, current

    ± (0.5% FS + one digit)

    Active power, reactive power

    ± (0.5% FS + one digit)

    Frequency

    ± 0.1 Hz

    Power factor

    ± 0.01 PF

    Active energy

    ± 0.5% (only for reference, not for meterage)

    Reactive energy

    ± 1.0% (only for reference, not for meterage)

    Source

    Scope

    AC 220V, 50/60Hz

    Consumption

    <5VA

    Safety

    Withstand voltage

    Input and source

    >2kV 50Hz / 1min

    Input and output

    >1kV 50Hz / 1min

    Output and source

    >2kV 50Hz / 1min

    Insulating resistance

    Any two of input, output, source, casing >20MΩ

    Environment

    Temperature

    Operation: -10 ~ 50°C

    Storage: -25 ~ 70°C

    Humidity

    ≤85% RH, free of wet and corrosive gas

    Elevation

    ≤3000m

    📦 Function & Shape / Model Selection Table

    Function & Shape / Model

    Measure & Display

    Shape Code (Figure Inside)

    Selected Additional Functions

    Phase Voltage V

    Line Voltage

    Current

    Frequency

    Power Factor

    Active Power

    Total Reactive Power

    Total Apparent Power

    Each Phase Power Factor

     

    Each Phase

    Apparent Power

    Active Energy

    Reactive Energy

    ⑨ 96×96

    ⑧ 80×80

    ⑦ 72×72

    Communication Interface: RS485

    4-Channel Switch Outputs

    4-Channel Switch Input

    4-Channel Analog Output

    Harmonic

    SFS-□S3-3E

     

     

     

     

     

     

     

    +

     

     

     

     

    SFS-□SY-3E

     

     

     

     

    +

     

     

     

     

    SFN-□S3-3E

     

     

     

     

     

     

     

     

    +

     

     

     

     

    SFN-□SY-3E

    +

     

     

     

     

    SFN-□S3-3E+4DO

     

     

     

     

     

     

     

    +

    +

     

     

     

    SFN-□SY-3E+4DO

     

     

    +

    +

     

     

     

    SFN-□S3-3E+4DI

     

     

     

     

     

     

     

    +

     

    +

     

     

    SFN-□SY-3E+4DI

     

     

    +

     

    +

     

     

    SFN-□S3-3E+4AO

     

     

     

     

     

     

     

    +

     

     

    +

     

    SFN-□SY-3E+4AO

     

     

     

     

    +

     

     

    +

     

    SFN-□SY-3E+H

     

     

     

    +

     

     

     

    +

    Frequently Asked Questions (FAQ)
    What types of network configurations does this power meter support?
    This power meter supports both three-phase three-wire and three-phase four-wire network configurations, making it suitable for a wide range of industrial and commercial power systems with input voltage up to AC 500V.
    What communication protocol and interface does the meter use?
    The meter uses RS485 communication interface with the MODBUS_RTU protocol. It supports baud rates of 1200, 2400, 4800, and 9600 bps, making it easily networkable with PLCs and industrial control computer software.
    What are the available optional extended function modules?
    The device supports several optional extension modules: 4-channel analog output (0–20mA / 4–20mA), 4-channel switching value output (normally open relay, AC 240V/2A), 4-channel dry contact switching input, and a harmonic measurement module. Customers can select the combination that best suits their application.
    What is the measurement accuracy of this power meter?
    The meter provides high accuracy across multiple parameters: voltage and current at ±(0.5% FS + one digit), active and reactive power at ±(0.5% FS + one digit), frequency at ±0.1 Hz, and power factor at ±0.01 PF. Energy readings are for reference only and not intended for billing (meterage) purposes.
    What are the operating environment requirements for this device?
    The device is designed for operation in temperatures ranging from -10°C to 50°C, with storage temperatures from -25°C to 70°C. Humidity should be ≤85% RH, free from wet and corrosive gases. The device can be installed at elevations up to 3,000 meters above sea level.
    What display type does this meter use, and what are the available panel sizes?
    The meter uses an LCD display with blue backlighting for clear readability. It is available in three standard panel sizes: 96×96mm (Model Code ⑨), 80×80mm (Model Code ⑧), and 72×72mm (Model Code ⑦), allowing flexible integration into various panel and switchgear configurations.