Multifunctional LED Power Instrument from China Suppliers | High-Precision Measuring Factory
Product Overview
Many kinds of extended function modules for choosing: four-channel analog quantity(0~20mA/4~20mA)output can realize the transmitting output function of electrical quantity; four-channel switching value input and four-channel switching value output to realize the local or long-range switch signal monitoring and control output function (function of "remote signaling" and "remote control"). The instrument can directly replace conventional power transmitter, measuring indicating instrument, electric energy measuring instrument and the related auxiliary unit. With modular structural design, users can choose the most economical functional configuration according to the actual requirement, which is highly cost-effective.
Directly replaces conventional transmitters and meters with cost-effective modular options.
Supports remote signaling, remote control, and transmitting output of electrical quantities.
It is widely used in occasions of energy management systems, supply and distribution network automation, district power control and complete sets of switchgear. It has the advantages of convenient installment and maintenance sample wiring, small quantity, programmable input parameters and capable of the network with different PLC, industry control computer communications.
Technical Parameters
| Technical parameters | Index | ||
|---|---|---|---|
| Input | Net work | Three-phase three-wire, three-phase four-wire | |
| Voltage | Rated value | AC 0~500V | |
| Over load | Consistent 1.2 times instantaneous, 2 times /30s | ||
| Consumption | <0.5VA (each phase) | ||
| Impedance | >500kΩ | ||
| Current | Rated value | AC 1A, 5A | |
| Over load | Consistent: 1.2 times instantaneous, 2 times /11s | ||
| Impedance | <2mΩ | ||
| Frequency | 45-65Hz | ||
| Output | Electric energy | Output mode | Two-channel open-collector, optical coupling pulse output |
| Pulse constant | Active 3200imp/kwh, Reactive 3200imp/kvarh | ||
| Start | On the condition of rated voltage, reference frequency and cosφ = 1.0, when load operational current is 0.01In, it can start and measure the electric energy continuously. | ||
| Creep | When exerting 115% rated voltage and no current in the current circuitry, the instrument is with no electric energy accumulation and pulse output. | ||
| Output | Communication | Output mode | RS485 |
| Protocol | MODBUS-RTU | ||
| Baud rate | 1200, 2400, 4800, 9600 | ||
| Analog quantity | Channel quantity | 4 channels | |
| Output mode | 0-20mA, 4-20mA | ||
| Load ability | <400Ω | ||
| Switching value | Channel quantity | 4 channels | |
| Output mode | Normally open relay contact output | ||
| Contact capability | AC 240V/2A | ||
| Switching value input | Four channel dry contact input modes | ||
| Display mode | LED (RED) | ||
| Measuring accuracy | Voltage, current | ± (0.5%FS+1 digit) | |
| Active power, reactive power | ± (0.5%FS+1 digit) | ||
| Frequency | ± 0.1Hz | ||
| Power factor | ± 0.01PF | ||
| Active energy | ± 0.5% (only for reference, not for meterage) | ||
| Reactive energy | ± 1.0% (only for reference, not for meterage) | ||
| Source | Scope | AC 220V, 50/60Hz | |
| Consumption | <5VA | ||
| Safety | Withstand voltage | Input and source | >2kV 50Hz/1min |
| Input and output | >1kV 50Hz/1min | ||
| Output and source | >2kV 50Hz/1min | ||
| Insulating resistance | Any two of input, output, source, casing >20MΩ | ||
| Environment | Temperature | Operation: -10 ~ 50°C | |
| Storage: -25 ~ 70°C | |||
| Humidity | ≤85%RH, free of wet and corrosive gas | ||
| Elevation | ≤3000m | ||
| Function & Shape / Model | Measure & Display | Shape Code | Selected Additional Functions | |||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Phase Voltage V | Line Voltage | Current | Frequency | Power Factor | Active Power | Total Reactive Power | Total Apparent Power | Each Phase Power Factor | Each Phase Reactive Power | Each Phase Active Power | Apparent Power | Active Energy | Reactive Energy | ⑨ 96×96 | ⑧ 80×80 | ⑦ 72×72 | RS485 | 4DO | 4DI | 4AO | Harmonic | |
| SFS-□S3-3E | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | |||||||||||
| SFS-□SY-3E | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | ||||||||
| SFN-□S3-3E | ● | ● | ● | ● | ● | ● | ● | √ | √ | + | ||||||||||||
| SFN-□SY-3E | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | √ | √ | + | ||||
| SFN-□S3-3E+4DO | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | ||||||||||
| SFN-□SY-3E+4DO | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | |||||
| SFN-□S3-3E+4DI | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | ||||||||||
| SFN-□SY-3E+4DI | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | |||||
| SFN-□S3-3E+4AO | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | ||||||||||
| SFN-□SY-3E+4AO | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | |||||||
| SFN-□SY-3E+H | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | √ | + | + | ||||||
Frequently Asked Questions
The instrument comes equipped with an RS485 communication interface utilizing standard MODBUS-RTU protocol, with selectable baud rates of 1200, 2400, 4800, and 9600 bps for seamless integration with PLCs and industrial control computers.
The device supports AC 0~500V rated voltage inputs and AC 1A / 5A rated current inputs, suitable for both three-phase three-wire and three-phase four-wire electrical power distribution networks.
Users can choose optional expansion modules including 4-channel analog output (0~20mA / 4~20mA), 4-channel digital/switching input (4DI dry contacts), 4-channel relay output (4DO normally open, AC 240V/2A), and harmonic measurement capabilities.
The series is available in three standard panel cutout dimensions: 96×96mm (Shape code ⑨), 80×80mm (Shape code ⑧), and 72×72mm (Shape code ⑦), providing flexible mounting options for switchgear panels.
It delivers high-precision measurements with ±(0.5%FS+1 digit) for voltage, current, active power, and reactive power; ±0.1Hz for frequency; ±0.01PF for power factor; and ±0.5% for active energy (reference indication).